Metal building roof curbs leak for four main reasons: the curb is fixed to a roof designed to move, water dams on the upslope side, galvanized welds rust through, or an adapter added during an RTU swap opens a new joint. Each is avoidable when the curb is specified as part of the roof system instead of the HVAC scope.

What a Roof Curb Does on a Metal Building

A roof curb is a raised frame that supports rooftop equipment, seals the roof opening beneath it, and diverts water around the unit.

On a metal building, the curb also has to handle thermal movement. Standing seam panels attach with sliding clips, so the roof plane shifts as the steel heats and cools. Roof curbs for metal roofs either move with the panels or sit on a separate structural support that isolates the unit from them.

Kansas City averages 36 days a year above 90°F and 41 nights below 20°F. Over a 100-foot panel run, metal roof expansion and contraction adds up to nearly an inch, and a curb fixed in place takes that stress at its seal.

Types of Metal Building Roof Curbs

The right curb depends on the unit’s weight and how it ties into the building.

Curb type What carries the unit Moves with the roof? Typical use Watch for
Floating structural curb The curb, attached to the roof panels Yes Smaller, bottom-ducted units Weight limits set by the roof and curb supplier
Double curb An inner curb tied to the building frame; an outer flashing curb seals to the panels Outer curb only Heavier units Counterflashing between the curbs must allow movement
Frame-mounted unit Steel legs or a frame carried to the structure No Heavy or oversized equipment Duct curb sized larger than the duct so the roof can slide
Curb adapter An adapter sitting on the existing curb Same as the curb below it RTU replacements Adds a joint, raises the unit, may add load

Heavier units often need a double curb. The weight limit for a single curb comes from the roof manufacturer and curb supplier, not a universal cutoff.

Rusted pipe penetration with corrosion streaks and patched sealant on an exposed-fastener metal roof

Why Metal Building Roof Curbs Leak

The Curb Is Pinned to a Roof Built to Float

A curb fastened rigidly to the structure, or set on stationary framing under a floating roof, locks the panels in place at that point. Movement concentrates at the curb flange until the seal fatigues. These leaks often appear after the roof has cycled through a season, not on the first rain.

Water Dams on the Upslope Side

Without a diverter, a small cricket built into the upslope end of the curb, water backs up against the curb wall and puts head pressure on the seal. Metal Construction Association (MCA) guidance calls for at least 12 inches between the panel ends and the diverter, and 6 inches between the curb sides and the panel seams.

The Curb Is Galvanized Steel

Welding burns off the coating on galvanized and Galvalume® steel curbs, and the welds rust first. MCA has documented a galvanized curb rusting at the welds in under a year. Its best practice is continuously welded .080-inch aluminum or 18-gauge stainless steel.

An Adapter Was Added During an RTU Swap

A roof curb adapter lets a new unit use the old curb and opening, but it adds a joint above the roof, raises the unit, and often adds weight. A heavier replacement unit needs the curb and the framing below it checked before it is set.

Condensate and Drill Shavings Were Left on the Roof

Condensate off copper coils corrodes metal roof coatings when it discharges onto the panels. Drill shavings rust in place. Both belong on the metal roof inspection checklist after any rooftop work.

How to Specify a Roof Curb on a Standing Seam Roof

Put these five requirements in the scope before equipment goes on the roof.

  1. Have the roof installer set the curb. Curb work often lands in the HVAC section of the spec, and most HVAC crews are not trained in metal roof waterproofing or thermal movement. MCA recommends involving the roof installer in every curb installation, including curbs added after the roof is in service.
  2. Use a curb matched to the roof system. On a Butler MR-24® standing seam roof system, that is Butler’s all-aluminum, internal-flange curb, with its fasteners on the interior flange. MCA notes that skipping the manufacturer’s curb details could void a weathertightness warranty.
  3. Shingle the curb into the roof. Correct roof curb installation laps the flange under the panels on the upslope end and over them on the downslope end, with the 12-inch and 6-inch clearances held.
  4. Check the structure before setting a heavier unit. MAR’s Missouri-registered professional engineer reviews whether the purlins and framing can carry the new load and whether the unit needs a double curb.
  5. Route condensate and clean up daily. Pipe condensate in PVC to a gutter or drain, and sweep drill shavings off the roof at the end of each workday.

Repairing a Leaking Roof Curb

Caulk does not fix a curb leak caused by movement or a missing diverter. It cracks again at the next temperature swing.

Confirm the curb is the source first. Water runs along purlins before it drips, so a stain near a unit does not prove the curb failed. Determine whether the leak is isolated or systemic.

A confirmed metal roof curb leak calls for one of three repairs:

  • Reflash: rework the roof curb flashing, closures, and sealant when the curb itself is sound and correctly placed.
  • Replace: swap a rusting galvanized curb for an aluminum curb matched to the roof profile.
  • Convert: add a structural inner curb and an outer flashing curb when the unit is too heavy for a floating curb.

MAR, a Certified Butler Builder®, reflashes and replaces curbs through its metal building repair services and handles larger reroof scopes through commercial roofing.

Base of a rooftop HVAC unit on a metal roof with a PVC condensate line and staining where the unit meets the panels

Frequently Asked Questions

What is a roof curb on a metal building?

A roof curb is a raised frame that supports rooftop equipment and seals the opening beneath it. On a metal building, the curb also has to handle thermal movement, either by floating with the panels or by being isolated from them with a double curb.

Can a new rooftop unit sit on the old curb?

Often, yes, with a curb adapter that matches the new unit’s footprint to the existing curb. The adapter adds a joint and may add weight, so check the old curb’s condition and the structure below first.

Who should install an HVAC roof curb, the HVAC contractor or the roofer?

The roof installer sets and flashes the curb, and the HVAC contractor sets the unit on it. Metal roof curbs depend on panel layout, lapping, and thermal movement, which fall outside most HVAC scopes.

Can a roof curb void a metal roof warranty?

Yes. MCA guidance notes that failing to follow the roof manufacturer’s curb details could void a weathertightness warranty. Check the warranty terms before adding any penetration.

Why did my roof curb start leaking months after installation?

Movement. A curb that restricts thermal movement holds through the first rain, then the seal fatigues as the panels expand and contract over a full season.